central air conditioner faults diagnosis
( RULE 0 )
IF complaint is "no cooling"
AND nothing works
THEN problem is no control voltage
( RULE 1 )
IF problem is no control voltage
AND control transformer is getting line voltage
AND control transformer output is zero volts
THENCON fault is burned out control transformer
( RULE 2 )
IF complaint is "no cooling"
ANDNOT nothing works
AND indoor fan will run
THEN problem is in condensing section
( RULE 3 )
IF problem is in condensing section
ANDNOT compressor will run
ANDNOT outdoor fan will run
ANDNOT line voltage is available to contactor
THENCON condensing unit main power is off
( RULE 4 )
IF problem is in condensing section
ANDNOT compressor will run
ANDNOT outdoor fan will run
AND line voltage is available to contactor
THEN problem is in contactor
( RULE 5 )
IF problem is in contactor
AND 24 volts is available to contactor coil
AND contactor coil resistance is infinite ohms
THENCON contactor coil is open
( RULE 6 )
IF problem is in condensing section
ANDNOT compressor will run
AND outdoor fan will run
AND voltage exists across contactor compressor contact
THENCON fault is contactor compressor contact is open
( RULE 7 )
IF problem is in condensing section
ANDNOT outdoor fan will run
AND compressor will run
AND voltage exists across contactor outdoor fan contact
THENCON fault is contactor outdoor fan contact is open
( RULE 8 )
IF problem is in condensing section
ANDNOT compressor will run
AND outdoor fan will run
ANDNOT voltage exists across contactor compressor contact
ANDNOT compressor common amps are 52 amps
THEN problem is in compressor
( RULE 9 )
IF problem is in compressor
ANDNOT compressor will run
AND "R" to "C" resistance is infinity
ANDNOT "S" to "C" resistance is infinity
THENCON fault is open compressor run winding
( RULE 10 )
IF problem is in condensing section
ANDNOT compressor will run
AND outdoor fan will run
ANDNOT voltage exists across contactor compressor contact
AND compressor common amps are 52 amps
THEN problem is in compressor start circuit
( RULE 11 )
IF problem is in compressor start circuit
AND "S" to "C" resistance is infinity
THENCON fault is open compressor start winding
( RULE 12 )
IF problem is in compressor start circuit
ANDNOT "S" to "C" resistance is infinity
THEN problem is in compressor capacitor
( RULE 13 )
IF problem is in compressor capacitor
AND discharged capacitor shows infinite resistance
THENCON fault is open compressor capacitor
( RULE 14 )
IF problem is in condensing section
AND compressor will run
ANDNOT outdoor fan will run
ANDNOT voltage exists across contactor outdoor fan contact
THEN problem is in outdoor fan or capacitor
( RULE 15 )
IF problem is in outdoor fan or capacitor
AND outdoor fan run lead amperage is zero
THENCON fault is open outdoor fan run winding
( RULE 16 )
IF problem is in outdoor fan or capacitor
ANDNOT outdoor fan run lead amperage is zero
AND outdoor fan start lead amperage is zero
ANDNOT discharged capacitor shows infinite resistance
THENCON fault is open outdoor fan start winding
( RULE 17 )
IF problem is in outdoor fan or capacitor
ANDNOT outdoor fan run lead amperage is zero
AND outdoor fan start lead amperage is zero
AND discharged capacitor shows infinite resistance
THENCON fault is open outdoor fan capacitor
( RULE 18 )
IF complaint is "no cooling"
ANDNOT nothing works
ANDNOT indoor fan will run
AND voltage exists across fan relay N.O. contacts
THEN problem is in fan relay
( RULE 19 )
IF problem is in fan relay
AND voltage exists across fan relay N.O. contacts
AND relay coil resistance is infinity
THENCON fault is open relay coil
( RULE 20 )
IF problem is in fan relay
AND voltage exists across fan relay N.O. contacts
ANDNOT relay coil resistance is infinity
THENCON fault is relay contact stuck open
( RULE 21 )
IF complaint is "no cooling"
ANDNOT nothing works
ANDNOT indoor fan will run
ANDNOT voltage exists across fan relay N.O. contacts
AND fan high speed lead amperage is 0 amps
THENCON fault is open indoor fan high speed winding
( RULE 22 )
IFNOT complaint is "no cooling"
ANDNOT complaint is "not enough cooling"
AND complaint is "none"
THEN we had best check heating mode
( RULE 23 )
IF we had best check heating mode
AND fan switch is in "auto" position
ANDNOT indoor fan runs after call for heat
AND fan low speed lead amperage is 0 amps
THENCON fault is open indoor fan low speed winding
( RULE 24 )
IF complaint is "no cooling"
ANDNOT nothing works
ANDNOT indoor fan will run
ANDNOT voltage exists across fan relay N.O. contacts
ANDNOT fan high speed lead amperage is 0 amps
THEN problem is in fan starting circuit
( RULE 25 )
IF problem is in fan starting circuit
AND discharged capacitor shows infinite resistance
THENCON fault is open indoor fan capacitor
( RULE 26 )
IFNOT complaint is "no cooling"
AND complaint is "not enough cooling"
ANDNOT indoor section filter is dirty
THEN problem is in outdoor section
( RULE 27 )
IF problem is in outdoor section
AND complaint is "not enough cooling"
AND condensing coil is clean
AND condensing temp < 30 deg. above ambient
THENCON fault is low system refrigerant charge
( RULE 28 )
IFNOT complaint is "no cooling"
AND complaint is "not enough cooling"
AND indoor section filter is dirty
THENCON fault is dirty filter
( RULE 29 )
IF problem is in outdoor section
AND complaint is "not enough cooling"
ANDNOT condensing coil is clean
THENCON fault is dirty condensing coil
( RULE 30 )
IF problem is in condensing section
AND compressor will run
AND outdoor fan will run
ANDNOT compressor is continuously cycling
ANDNOT condensing unit main power breaker trips
AND hi & lo pressures are equal or nearly equal
THENCON fault is compressor valve failure
( RULE 31 )
IFNOT complaint is "no cooling"
ANDNOT complaint is "not enough cooling"
ANDNOT complaint is "none"
AND complaint is "outdoor unit makes knocking noise"
THENCON fault is broken compressor internal mount
( RULE 32 )
IFNOT complaint is "no cooling"
ANDNOT complaint is "not enough cooling"
ANDNOT complaint is "none"
AND complaint is "outdoor unit makes squealing noise"
AND noise is coming from outdoor fan
THENCON fault is worn outdoor fan motor bearings
( RULE 33 )
IFNOT complaint is "no cooling"
ANDNOT complaint is "not enough cooling"
ANDNOT complaint is "none"
AND complaint is "indoor unit makes squealing noise"
AND noise is coming from indoor fan
THENCON fault is worn indoor fan motor bearings
( RULE 34 )
IF problem is in condensing section
AND compressor will run
AND outdoor fan will run
ANDNOT compressor is continuously cycling
AND condensing unit main power breaker trips
AND condensing unit total current is less than 20 amps
THENCON fault is faulty condensing unit main power breaker
( RULE 35 )
IF problem is in condensing section
AND compressor will run
AND outdoor fan will run
AND compressor is continuously cycling
AND condensing unit voltage is less than 208 volts
THENCON fault is low main power voltage
( RULE 36 )
IF we had best check heating mode
AND fan switch is in "auto" position
AND indoor fan runs after call for heat
THENCON unit is fine - there are no faults